Well-X-trol
®
Sizing Example
•
(7) Determine the Well-X-trol volume
–
The volume is obtained by dividing the drawdown
in step 5 (
28 gals
) by the acceptance factor (
.31
)
determined from step 6
–
28 gals /.31
=
90 gallons
(cont.)