Sizing
the Well-X-trol®
–(5) Determine the Well-X-trol drawdown
by multiplying
(1) X (2)………………
____ gallons
–(6)
Determine acceptance factor using the pressures in (3) and (4)
and either the chart or the equation:
AF = 1 – ( P1+14.7) ∕ (P2+14.7)
–
AF = ____
(cont.)